Dew point and humidity calculator with psychrometric chart
Work out the dew point, relative humidity or temperature, plus absolute humidity, wet bulb and enthalpy of moist air, shown on a psychrometric chart.
Work out the dew point of air, the temperature at which it starts to condense, from its temperature and relative humidity. Any two of the three give the third: for example, the relative humidity for a measured dew point. It also gives the absolute and specific humidity, the wet bulb, the enthalpy and the air density, and places it on the psychrometric chart.
Formulas
This is the Magnus formula with the Alduchov and Eskridge constants (a = 17.625; b = 243.04 °C), within 0.1 °C from −40 to 50 °C. Vapour pressure and specific humidity come from:
The wet bulb uses Stull's empirical formula (2011), valid at sea level from −20 to 50 °C and 5 to 99 % humidity, within ±1 °C.
Condensation on walls, windows and pipes
A surface colder than the dew point gets wet. That is what happens at thermal bridges in a home in winter, on single-glazed windows and on uninsulated cold water or chilled water pipes. To prevent it, either warm the surface (insulation) or lower the humidity (ventilation or a dehumidifier).
Dew point chart
| Air | Dew point | Specific humidity | Wet bulb |
|---|---|---|---|
| 20 °C, 50 % | 9.3 °C | 7.2 g/kg | 13.7 °C |
| 20 °C, 70 % | 14.4 °C | 10.2 g/kg | 16.3 °C |
| 22 °C, 60 % | 13.9 °C | 9.9 g/kg | 16.8 °C |
| 25 °C, 50 % | 13.9 °C | 9.9 g/kg | 18.0 °C |
| 30 °C, 60 % | 21.4 °C | 16.0 g/kg | 24.0 °C |
Saturation humidity (1 atm)
The most the air can hold at each temperature, 100 % relative humidity. It is the saturation curve on the chart:
| Temperature | Maximum specific humidity |
|---|---|
| -10 °C | 1.8 g/kg |
| -5 °C | 2.6 g/kg |
| 0 °C | 3.8 g/kg |
| 5 °C | 5.4 g/kg |
| 10 °C | 7.6 g/kg |
| 15 °C | 10.6 g/kg |
| 20 °C | 14.7 g/kg |
| 25 °C | 20.0 g/kg |
| 30 °C | 27.1 g/kg |
| 35 °C | 36.5 g/kg |
| 40 °C | 48.8 g/kg |
| 45 °C | 65.0 g/kg |
| 50 °C | 86.4 g/kg |
Worked example
A living room at 22 °C and 60 % humidity: γ = ln(0.6) + 17.625 · 22 / 265.04 = −0.511 + 1.463 = 0.952; Td = 243.04 · 0.952 / (17.625 − 0.952) = 13.9 °C. Any wall below 13.9 °C condenses. The air holds 9.9 g of water per kg and its wet bulb is 16.8 °C.
Frequently asked questions
What is the dew point?
The temperature to which air must be cooled, without changing its moisture, for the vapour to start condensing. If a wall, a window or a pipe is colder, it gets wet.
What is the dew point at 22 °C and 60 %?
About 13.9 °C: any surface colder than that in the room will have condensation.
What is the difference between relative and absolute humidity?
Absolute humidity is the water actually there (g/m³). Relative humidity compares the vapour with the most the air could hold at its temperature: heating air without adding water lowers the relative humidity and leaves the absolute one unchanged.
What humidity is right at home?
Between 40 and 60 % relative humidity. Above it, mould and condensation appear on cold spots; below it, dry eyes and throat.