Pipe insulation calculator: heat loss and savings
Calculate the heat loss of a pipe with and without insulation, its surface temperature, the energy lost per year and the insulation thickness for a given loss.
A hot uninsulated pipe is a radiator: a 2-inch steam pipe loses almost half a kilowatt per metre. With this calculator you find out how much heat your pipe loses with the insulation it has (or without it), the temperature its surface reaches, how much energy goes to waste each year and how much you save. And the other way round: the insulation thickness you need to stay below a loss per metre.
How to use the calculator
- Enter the fluid temperature, the air temperature and the pipe outside diameter.
- Choose the insulation (it sets its conductivity) and the outer finish.
- Enter the thickness to get the loss, or the loss per metre you can accept to get the thickness. With a thickness of 0 you calculate the bare pipe.
- With the length and the hours per year you will see the energy lost and saved.
Heat loss formula
Where q is the heat loss per metre of pipe (W/m), Tf the fluid temperature, Ta the air temperature, Do the pipe outside diameter, Ds = Do + 2 · e the outside diameter of the insulation, λ the insulation conductivity (W/(m·K)) and h the heat transfer coefficient from the surface to the air (W/(m²·K)).
h adds natural convection, hc ≈ 1.32 · (ΔT / Ds)0.25, and radiation, hr = ε · σ · (Ts⁴ − Ta⁴) / (Ts − Ta), which depends on the emissivity ε of the finish and the surface temperature Ts. As Ts is not known, the calculator finds it by iteration. The resistance of the steel pipe wall is negligible.
Insulation conductivity
| Insulation | λ (W/(m·K)) at 50 °C | Maximum temperature |
|---|---|---|
| Polyurethane (PUR) | 0.025 to 0.030 | 110 to 130 °C |
| Elastomeric foam | 0.034 to 0.038 | 105 to 150 °C |
| Glass wool | 0.035 to 0.040 | 250 to 450 °C |
| Mineral wool (rock wool) | 0.037 to 0.045 | 650 to 750 °C |
| Cellular glass | 0.040 to 0.050 | 430 °C |
| Calcium silicate | 0.055 to 0.065 | 1000 °C |
Conductivity rises with the mean temperature of the insulation: at 150 °C, mineral wool is around 0.050.
Worked example
100 m of DN 50 steel pipe (60.3 mm outside diameter) with steam at 150 °C, air at 20 °C, 50 mm of mineral wool (λ = 0.040) with aluminium sheet, 6000 hours per year:
With steam at 5 bar (hfg ≈ 2086 kJ/kg), that is about 445 tonnes of steam per year.
Frequently asked questions
How much does insulating a pipe save?
A lot: with 50 mm of mineral wool, a steam pipe loses 85 to 95 % less heat than bare. A bare DN 50 pipe at 150 °C loses about 450 W per metre.
Why does the finish matter?
Because the surface also loses heat by radiation. A shiny aluminium sheet radiates little and stays hotter to the touch; a painted surface radiates more and stays cooler, although the total losses change little.
What surface temperature is safe?
To avoid burns, it is recommended that it does not exceed about 50 to 60 °C in walkways. Building regulations also set minimum insulation thicknesses in heating installations.
Does it work for cold pipes?
Yes: if the fluid is colder than the air, the loss comes out as a heat gain. In chilled water or refrigeration it is also important that the surface does not fall below the dew point, so that it does not condense.