Short-circuit current calculator (low voltage)
Calculate the maximum short-circuit current at the transformer terminals and at the end of the line, the minimum phase-neutral fault and breaking capacity.
The short-circuit current (Icc) is the current that flows when two phases, or a phase and the neutral, touch with nothing in between. Only the impedances of the grid, the transformer and the cables limit it. With this calculator you get the maximum three-phase Icc at the transformer terminals and at the end of a line, the minimum phase-neutral Icc and the breaking capacity the circuit breakers need, following the impedance method of IEC 60909 (UNE-EN 60909-0) simplified for low voltage.
How to use the calculator
- Enter the transformer data: rating, secondary voltage and short-circuit voltage (ucc), which are on its nameplate. If you know its load losses, the resistive part is uRr = losses ÷ rating × 100.
- The short-circuit power of the grid is given by the utility. If you do not know it, leave 500 MVA; with 0 it is calculated with an infinite grid.
- Choose the cable: copper or aluminum, insulation, cross-section, parallel cables per phase and length.
- You get the minimum Icc at the end of the line. The other way round: enter the minimum Icc you need (the magnetic trip current of the circuit breaker) and the calculator gives you the maximum length of the line or, if you leave the cross-section empty, the minimum cross-section.
Short-circuit current formula
The maximum Icc is that of a three-phase short circuit:
Where U is the phase-to-phase voltage (V), c the voltage factor and Zk the total impedance up to the fault (Ω), the sum of the grid, transformer and cable impedances (adding resistances and reactances separately):
| Section | Impedance | Resistance and reactance |
|---|---|---|
| Grid | ZQ = 1.1 · U² / Scc | XQ = 0.995 · ZQ, RQ = 0.1 · XQ |
| Transformer | ZT = ucc · U² / S | RT = uRr · U² / S, XT = √(ZT² − RT²) |
| Cable | ZL = √(RL² + XL²) | RL = L / (γ · s · n), XL = 0.08 mΩ/m · L / n |
γ is the conductivity of the conductor (m/(Ω·mm²)), s the cross-section (mm²), n the parallel cables per phase and L the length (m). For the maximum Icc, the cable is cold (20 °C). The peak current, used for the making capacity, is ip = κ · √2 · Icc, with κ = 1.02 + 0.98 · e−3R/X.
Voltage factor c
| Case | c |
|---|---|
| Maximum Icc, low voltage with +6 % tolerance | 1.05 |
| Maximum Icc, low voltage with +10 % tolerance | 1.10 |
| Minimum Icc, low voltage | 0.95 |
In Spain the supply voltage may vary by ±7 % (Royal Decree 1955/2000), more than 6 %: the prudent choice is c = 1.10.
Minimum phase-neutral Icc
The smallest one is that of a fault between one phase and the neutral at the end of the line, with the cable hot. It is calculated with the loop impedance: out along the phase and back along the neutral.
U₀ = U/√3 is the phase-to-neutral voltage. In a Dyn transformer, the zero-sequence impedance is almost equal to the positive-sequence one, so the transformer counts once; the medium-voltage grid does not pass the zero sequence to the secondary and counts ⅔. The cable, with the neutral the same size, counts twice and with its resistance at operating temperature:
| Conductor | γ at 20 °C | γ at 70 °C (PVC) | γ at 90 °C (XLPE, EPR) |
|---|---|---|---|
| Copper | 56 | 48 | 44 |
| Aluminum | 35 | 30 | 28 |
Conductivities in m/(Ω·mm²), those of the Technical Application Guide (Guía técnica de aplicación) of Spain's low-voltage electrical code (REBT).
The practical formula of the REBT Guide
When what lies upstream is unknown, the Technical Application Guide of Spain's Low-Voltage Regulation proposes:
U is the phase-to-neutral voltage (230 V), S the cross-section (mm²), ρ the resistivity at 20 °C (Ω·mm²/m) and L the length of the line (m). The 0.8 assumes that 80 % of the voltage remains at the start of the line; the 1.5, that the cable resistance rises by 50 % with the heating of the short circuit, and the 2, out along the phase and back along the neutral. It ignores the reactance, so it is valid for long lines or small cross-sections. Close to the transformer it would give more current than there is at the terminals: in that case the calculator does not show it.
Breaking capacity of the circuit breaker
Each circuit breaker must be able to break the maximum Icc at the point where it is installed. The calculator proposes the next standard breaking capacity up:
| Maximum Icc up to | Breaking capacity |
|---|---|
| 6 kA | 6 kA |
| 10 kA | 10 kA |
| 15 kA | 15 kA |
| 25 kA | 25 kA |
| 36 kA | 36 kA |
| 50 kA | 50 kA |
| 70, 100 or 150 kA | Air circuit breakers or high-breaking-capacity molded-case circuit breakers |
Worked example
630 kVA transformer, 400 V, ucc = 4 % and uRr = 1 %, 500 MVA grid and c = 1.10. 95 mm² XLPE copper line, 80 m long.
The cold cable has RL = 80 / (56 · 95) = 15.04 mΩ and XL = 0.08 · 80 = 6.4 mΩ. Adding up: R = 17.61 mΩ, X = 16.59 mΩ and Zk = 24.19 mΩ.
For the minimum, the cable at 90 °C has 80 / (44 · 95) = 19.14 mΩ per conductor. The loop adds up to R = 2.56 + 2 · 19.14 = 40.84 mΩ and X = 10.07 + 2 · 6.4 = 22.87 mΩ, |Z| = 46.81 mΩ:
With the practical formula: 0.8 · 230.94 · 95 / (1.5 · 0.01786 · 2 · 80) ≈ 4095 A. A 250 A curve C circuit breaker (tripping at up to 2500 A) protects this line well.
Frequently asked questions
What is the maximum short-circuit current used for?
To choose the breaking capacity of the circuit breakers: each one must be able to break the largest short-circuit current that can occur where it is installed. The main breaker of the panel, at least the Icc at the transformer terminals.
And the minimum one?
To check that the protection trips: the minimum Icc, at the end of the line and between phase and neutral, must be higher than the magnetic trip current of the circuit breaker (for example, 10 times its rated current on curve C). If not, the line is too long or too thin for that device.
What is the voltage factor c?
A coefficient from IEC 60909 that accounts for the voltage being above nominal. In low voltage it is 1.05 if the tolerance is +6 % and 1.10 if it is +10 %. For the minimum Icc, 0.95 is used.
Why does the practical formula give a different value?
Because it assumes that 80 % of the voltage remains at the start of the line, without knowing the transformer, and it ignores the cable reactance. On long lines it gives similar values; on short lines close to the transformer, the one calculated with the impedances is more accurate.
What do I enter if I do not know the short-circuit power of the grid?
Leave 500 MVA, a usual value in medium-voltage grids. With 0 an infinite grid is assumed, the worst case for the maximum Icc. It has little influence on the low-voltage Icc: the transformer dominates.