Short-circuit current calculator (low voltage)

Calculate the maximum short-circuit current at the transformer terminals and at the end of the line, the minimum phase-neutral fault and breaking capacity.

Fill in 2 of the 3 fields and the missing one is calculated. You can type in any of them.

On the nameplate. Usually 4 % up to 630 kVA and 6 % above.
%
Load losses ÷ rating. If you do not know it, leave 1 %.
%
Given by the utility. If you do not know it, leave 500 MVA. With 0, infinite grid.
In Spain the supply voltage may vary by ±7 %: use 1.10.
The neutral, the same size as the phases.
Enter it (the magnetic trip current of the circuit breaker) to get the maximum length.
Maximum three-phase Icc at the transformer terminals—
Maximum three-phase Icc at the end of the line—
Peak current at the terminals (ip)—
Minimum phase-neutral Icc at the terminals—
Minimum Icc by the practical formula (0.8 · U · S / (1.5 · ρ · 2L))—
Standard cross-section that complies—
Breaking capacity of the circuit breaker at the terminals—
Breaking capacity at the end of the line—
Grid impedance—
Transformer impedance—
Cable impedance (one phase, 20 °C)—
Total impedance up to the fault—

Use this calculator for reference only, as we cannot guarantee that the results are free of errors.

Disclaimer

https://dyaii.es/en/short-circuit-current-calculator/

Advertisement

The short-circuit current (Icc) is the current that flows when two phases, or a phase and the neutral, touch with nothing in between. Only the impedances of the grid, the transformer and the cables limit it. With this calculator you get the maximum three-phase Icc at the transformer terminals and at the end of a line, the minimum phase-neutral Icc and the breaking capacity the circuit breakers need, following the impedance method of IEC 60909 (UNE-EN 60909-0) simplified for low voltage.

How to use the calculator

  1. Enter the transformer data: rating, secondary voltage and short-circuit voltage (ucc), which are on its nameplate. If you know its load losses, the resistive part is uRr = losses ÷ rating × 100.
  2. The short-circuit power of the grid is given by the utility. If you do not know it, leave 500 MVA; with 0 it is calculated with an infinite grid.
  3. Choose the cable: copper or aluminum, insulation, cross-section, parallel cables per phase and length.
  4. You get the minimum Icc at the end of the line. The other way round: enter the minimum Icc you need (the magnetic trip current of the circuit breaker) and the calculator gives you the maximum length of the line or, if you leave the cross-section empty, the minimum cross-section.

Short-circuit current formula

The maximum Icc is that of a three-phase short circuit:

Icc = c · U / (√3 · Zk)

Where U is the phase-to-phase voltage (V), c the voltage factor and Zk the total impedance up to the fault (Ω), the sum of the grid, transformer and cable impedances (adding resistances and reactances separately):

Zk = √((RQ + RT + RL)² + (XQ + XT + XL)²)
SectionImpedanceResistance and reactance
GridZQ = 1.1 · U² / SccXQ = 0.995 · ZQ, RQ = 0.1 · XQ
TransformerZT = ucc · U² / SRT = uRr · U² / S, XT = √(ZT² − RT²)
CableZL = √(RL² + XL²)RL = L / (γ · s · n), XL = 0.08 mΩ/m · L / n

γ is the conductivity of the conductor (m/(Ω·mm²)), s the cross-section (mm²), n the parallel cables per phase and L the length (m). For the maximum Icc, the cable is cold (20 °C). The peak current, used for the making capacity, is ip = κ · √2 · Icc, with κ = 1.02 + 0.98 · e−3R/X.

Advertisement

Voltage factor c

Casec
Maximum Icc, low voltage with +6 % tolerance1.05
Maximum Icc, low voltage with +10 % tolerance1.10
Minimum Icc, low voltage0.95

In Spain the supply voltage may vary by ±7 % (Royal Decree 1955/2000), more than 6 %: the prudent choice is c = 1.10.

Minimum phase-neutral Icc

The smallest one is that of a fault between one phase and the neutral at the end of the line, with the cable hot. It is calculated with the loop impedance: out along the phase and back along the neutral.

Icc min = 0.95 · U₀ / |⅔ · ZQ + ZT + 2 · ZL|

U₀ = U/√3 is the phase-to-neutral voltage. In a Dyn transformer, the zero-sequence impedance is almost equal to the positive-sequence one, so the transformer counts once; the medium-voltage grid does not pass the zero sequence to the secondary and counts ⅔. The cable, with the neutral the same size, counts twice and with its resistance at operating temperature:

Conductorγ at 20 °Cγ at 70 °C (PVC)γ at 90 °C (XLPE, EPR)
Copper564844
Aluminum353028

Conductivities in m/(Ω·mm²), those of the Technical Application Guide (Guía técnica de aplicación) of Spain's low-voltage electrical code (REBT).

The practical formula of the REBT Guide

When what lies upstream is unknown, the Technical Application Guide of Spain's Low-Voltage Regulation proposes:

Icc = 0.8 · U · S / (1.5 · ρ · 2 · L)

U is the phase-to-neutral voltage (230 V), S the cross-section (mm²), ρ the resistivity at 20 °C (Ω·mm²/m) and L the length of the line (m). The 0.8 assumes that 80 % of the voltage remains at the start of the line; the 1.5, that the cable resistance rises by 50 % with the heating of the short circuit, and the 2, out along the phase and back along the neutral. It ignores the reactance, so it is valid for long lines or small cross-sections. Close to the transformer it would give more current than there is at the terminals: in that case the calculator does not show it.

Breaking capacity of the circuit breaker

Each circuit breaker must be able to break the maximum Icc at the point where it is installed. The calculator proposes the next standard breaking capacity up:

Maximum Icc up toBreaking capacity
6 kA6 kA
10 kA10 kA
15 kA15 kA
25 kA25 kA
36 kA36 kA
50 kA50 kA
70, 100 or 150 kAAir circuit breakers or high-breaking-capacity molded-case circuit breakers
Also check the minimum Icc: it must be higher than the magnetic trip current of the circuit breaker protecting the line (on curve C, between 5 and 10 times its rated current; on curve B, between 3 and 5; on curve D, between 10 and 20). If it is not, shorten the line or increase the cross-section.

Worked example

630 kVA transformer, 400 V, ucc = 4 % and uRr = 1 %, 500 MVA grid and c = 1.10. 95 mm² XLPE copper line, 80 m long.

ZQ = 1.1 · 400² / 500,000,000 = 0.352 mΩ (RQ = 0.035 mΩ, XQ = 0.350 mΩ)
ZT = 0.04 · 400² / 630,000 = 10.16 mΩ (RT = 2.54 mΩ, XT = 9.84 mΩ)
Icc at the terminals = 1.1 · 400 / (√3 · 10.51 mΩ) ≈ 24.18 kA → breaking capacity of 25 kA

The cold cable has RL = 80 / (56 · 95) = 15.04 mΩ and XL = 0.08 · 80 = 6.4 mΩ. Adding up: R = 17.61 mΩ, X = 16.59 mΩ and Zk = 24.19 mΩ.

Icc at the end = 1.1 · 400 / (√3 · 24.19 mΩ) ≈ 10.50 kA → breaking capacity of 15 kA

For the minimum, the cable at 90 °C has 80 / (44 · 95) = 19.14 mΩ per conductor. The loop adds up to R = 2.56 + 2 · 19.14 = 40.84 mΩ and X = 10.07 + 2 · 6.4 = 22.87 mΩ, |Z| = 46.81 mΩ:

Icc min = 0.95 · 230.94 / 0.04681 ≈ 4687 A

With the practical formula: 0.8 · 230.94 · 95 / (1.5 · 0.01786 · 2 · 80) ≈ 4095 A. A 250 A curve C circuit breaker (tripping at up to 2500 A) protects this line well.

Advertisement

Frequently asked questions

What is the maximum short-circuit current used for?

To choose the breaking capacity of the circuit breakers: each one must be able to break the largest short-circuit current that can occur where it is installed. The main breaker of the panel, at least the Icc at the transformer terminals.

And the minimum one?

To check that the protection trips: the minimum Icc, at the end of the line and between phase and neutral, must be higher than the magnetic trip current of the circuit breaker (for example, 10 times its rated current on curve C). If not, the line is too long or too thin for that device.

What is the voltage factor c?

A coefficient from IEC 60909 that accounts for the voltage being above nominal. In low voltage it is 1.05 if the tolerance is +6 % and 1.10 if it is +10 %. For the minimum Icc, 0.95 is used.

Why does the practical formula give a different value?

Because it assumes that 80 % of the voltage remains at the start of the line, without knowing the transformer, and it ignores the cable reactance. On long lines it gives similar values; on short lines close to the transformer, the one calculated with the impedances is more accurate.

What do I enter if I do not know the short-circuit power of the grid?

Leave 500 MVA, a usual value in medium-voltage grids. With 0 an infinite grid is assumed, the worst case for the maximum Icc. It has little influence on the low-voltage Icc: the transformer dominates.