Electrical power calculator: active, reactive and apparent power and power factor
Power triangle calculator: active, reactive and apparent power, cos φ, voltage and current in three-phase, single-phase or DC from any three values.
One calculator for every power: active (P), reactive (Q), apparent (S) and the power factor (cos φ), together with the voltage and the current, in three-phase, single-phase or DC. Enter any three values and the rest are calculated, with the power triangle drawn to scale.
How to use the calculator
- Choose the type of current: three-phase, single-phase or DC (in DC the power factor is 1).
- Enter three values: for example voltage, current and cos φ; or the active power, cos φ and the voltage; or the active and reactive power plus the current.
- The other three are calculated instantly and are marked as Calculated. If you type in one of them, it becomes an input and the one that has gone longest without being touched is recalculated.
- Every field accepts any unit (W, kW, MW, hp…), and the “Decimals” button sets how many are shown.
The power triangle
Active, reactive and apparent power form a right triangle. The angle φ between P and S gives the power factor:
P is measured in kW, Q in kvar and S in kVA.
Power from voltage and current
In three-phase, V is the line-to-line voltage, and the factor √3 comes from going from the phase voltage to the line voltage in a balanced system.
Worked examples
Three-phase: a machine connected to 400 V draws 16 A with cos φ = 0.85.
Powers only: a 10 kW installation with cos φ = 0.85.
Power factor correction
To raise the power factor from cos φ₁ to cos φ₂, a capacitor bank is installed with a rating of:
With 10 kW, going from 0.85 to 0.95 takes 10 · (0.620 − 0.329) ≈ 2.9 kvar.
Typical power factor values
| Type of load | Approximate cos φ |
|---|---|
| Resistive loads (ovens, heating) | 1.00 |
| Induction motor at full load | 0.80 – 0.90 |
| Induction motor at half load | 0.65 – 0.75 |
| Induction motor at no load | 0.20 – 0.30 |
| Variable frequency drive (line side) | ≈ 0.95 |
Always use the nameplate value when you have it.
Quick current table at 400 V
Approximate three-phase current for cos φ = 0.85.
| Power (kW) | Current (A) |
|---|---|
| 1.1 | 1.9 |
| 2.2 | 3.7 |
| 5.5 | 9.3 |
| 11 | 18.7 |
| 22 | 37.4 |
| 45 | 76.4 |
Frequently asked questions
Which values do I have to enter?
Any three among voltage, current, power factor and the three powers, for example voltage, current and cos φ, or the active and reactive power plus the voltage. The rest are calculated automatically.
Why does √3 appear in three-phase?
Because the line-to-line voltage is used. In a balanced system, the line voltage is √3 times the phase voltage, and that factor carries over to the total power.
What is the difference between kW and kVA?
kW (active power) is the useful power, the part that is turned into work or heat. kVA (apparent power) also includes the reactive power and is what sizes transformers, generators and cables.
What is a good power factor?
Above 0.95. Below that, the utility may charge a penalty for the reactive energy consumed.
Does it work for unbalanced loads?
No. With unbalanced three-phase loads you have to calculate the power of each phase separately and add them up.
Related calculators
- Battery life calculator (Ah, Wh and Peukert)
- Voltage drop calculator and wire size
- Delta to wye (Δ-Y) conversion calculator for resistors and impedances
- Power factor correction calculator: capacitor bank sizing in kVAR and µF
- Cable tray bend and offset calculator
- kW to amps calculator: three-phase, single-phase and DC current