Earth resistance calculator: ground rods, ring and grid
Calculate the resistance of an earthing system with ground rods, buried conductor, ring, plate or grid (ITC-BT-18), the rods you need and the RCD check.
The earthing system carries the current of a fault into the ground so that no exposed metal part is left at a dangerous voltage. The lower its resistance, the lower that voltage. With this calculator you get the resistance of an earthing system with ground rods, buried conductor, ring, plate or grid according to ITC-BT-18 of Spain's Low-Voltage Regulation (REBT), and also the other way round: how many rods or what length you need for a given resistance. It also checks whether it complies with the RCD (residual-current device) you have.
How to use the calculator
- Choose the electrode: vertical ground rod, conductor buried horizontally, ring around the building, plate or grid.
- Choose the soil (its resistivity is filled in) or enter the resistivity you have measured.
- Enter the length (the perimeter for the plate) and how many identical electrodes you install in parallel. You get the resistance.
- The other way round: enter the resistance you want and the number of rods is calculated (or the length, if that is what you leave empty). With a measured resistance, the soil resistivity is calculated.
- Choose the limit voltage and the RCD sensitivity to check whether the earthing system complies.
ITC-BT-18 formulas
Table 5 of ITC-BT-18 gives these formulas to estimate the earth resistance from the soil resistivity ρ (Ω·m):
| Electrode | Earth resistance (Ω) | Data |
|---|---|---|
| Vertical ground rod | R = ρ / L | L: length of the rod (m) |
| Conductor buried horizontally | R = 2 · ρ / L | L: length of the conductor (m) |
| Buried plate | R = 0.8 · ρ / P | P: perimeter of the plate (m) |
The ring is a horizontally buried conductor that surrounds the building, so it is calculated with R = 2 · ρ / L, with L the length of the ring. For the grid, which is not in the table, the calculator uses Laurent's formula:
Where r = √(A/π) is the radius of the circle with the same area as the grid and L the total length of its conductors.
Several rods in parallel
With n identical electrodes in parallel, the resistance is approximately:
Soil resistivity
Average values from table 4 of ITC-BT-18, for approximate calculations:
| Soil | Resistivity (Ω·m) |
|---|---|
| Arable and fertile land, compact and moist fill | 50 |
| Poorly fertile arable fill and other fill | 500 |
| Bare stony ground, dry permeable sand | 3000 |
Indicative values from table 3:
| Soil | Resistivity (Ω·m) |
|---|---|
| Marshland | from a few units to 30 |
| Silt | 20 to 100 |
| Humus | 10 to 150 |
| Wet peat | 5 to 100 |
| Plastic clay | 50 |
| Marl and compact clay | 100 to 200 |
| Jurassic marl | 30 to 40 |
| Clayey sand | 50 to 500 |
| Siliceous sand | 200 to 3000 |
| Stony ground covered with grass | 300 to 500 |
| Bare stony ground | 1500 to 3000 |
| Soft limestone | 100 to 300 |
| Compact limestone | 1000 to 5000 |
| Fissured limestone | 500 to 1000 |
| Slate | 50 to 300 |
| Mica and quartz rock | 800 |
| Weathered granite and sandstone | 1500 to 10,000 |
| Highly weathered granite and sandstone | 100 to 600 |
When the table gives a range, the calculator takes the highest value, the worst case. The real resistivity depends on moisture and temperature: for a major installation, measure it with an earth tester (Wenner method).
Checking with the RCD
ITC-BT-18 requires that no exposed conductive part can produce touch voltages above 24 V in conductive (damp) locations or 50 V elsewhere. With an RCD of sensitivity IΔn, the highest fault current that flows without tripping it is IΔn, so:
| RCD | Maximum R with 50 V (Ω) | Maximum R with 24 V (Ω) |
|---|---|---|
| 30 mA | 1667 | 800 |
| 100 mA | 500 | 240 |
| 300 mA | 167 | 80 |
| 500 mA | 100 | 48 |
| 1 A | 50 | 24 |
The touch voltage when the RCD trips is Uc = R · IΔn.
Worked example
A 2 m ground rod in arable land (ρ = 50 Ω·m):
With a 30 mA RCD and 50 V, the maximum is 50 / 0.03 ≈ 1667 Ω: it complies easily, and the touch voltage would be 25 · 0.03 = 0.75 V.
In poorly fertile fill (ρ = 500 Ω·m), a 2 m rod gives 250 Ω. If you want to get down to 80 Ω to have a margin with a 300 mA RCD (maximum 167 Ω):
Spaced at least 2 · 2 = 4 m apart.
Frequently asked questions
What earth resistance does Spain's REBT require?
One that ensures no exposed conductive part can reach more than 24 V in damp locations or 50 V elsewhere (ITC-BT-18). With an RCD, that means R ≤ UL / IΔn: with a 30 mA one and 50 V, up to 1667 Ω; with a 300 mA one, up to 167 Ω.
How many ground rods do I need?
Enter the resistance you want and the calculator gives you the number of rods. Each rod of length L gives R = ρ / L; with n well-spaced rods, the resistance is approximately R / n.
How far apart should the rods be?
At least twice their length: with 2 m rods, 4 m or more. If they are closer, their areas of influence overlap and the resistance of the set is higher than R / n.
What resistivity do I enter if I have not measured it?
Choose the soil from the list: they are the values in tables 3 and 4 of ITC-BT-18. When the table gives a range, the calculator takes the highest value, the worst case. For a major installation, measure it (Wenner method) and enter the measured value.
Does the earth resistance change over time?
Yes: it rises in dry or frozen soil. That is why rods are driven more than 0.5 m deep and ITC-BT-18 requires the earthing system to be checked in the driest season of the year.