Transformer calculator: turns ratio, voltages and full-load current

Calculate the ratio of a single-phase or three-phase transformer: primary and secondary voltages, number of turns and rated (full-load) currents.

Fill in 4 of the 7 fields and the rest are calculated. You can type in any of them.

It only changes the turns ratio. Distribution transformers are usually Dyn11.
In three-phase, the phase-to-phase voltage.
Transformation ratio (m = U₁/U₂)—
Turns ratio (N₁/N₂)—
Volts per turn—
Secondary phase-to-neutral voltage—

Use this calculator for reference only, as we cannot guarantee that the results are free of errors.

Disclaimer

https://dyaii.es/en/transformer-calculator/

Advertisement

A transformer changes the voltage of an alternating current without changing its power: if the voltage goes down, the current goes up in the same proportion. With this calculator you get the transformation ratio, the number of turns and the rated currents of the primary and the secondary of a single-phase or three-phase transformer, and also the other way round: the missing voltage, power or turns.

How to use the calculator

  1. Choose whether the transformer is three-phase or single-phase. In three-phase, also choose the connection of the windings (on the nameplate: Dyn11, Yyn0…).
  2. Of these seven values, enter four: rating, primary and secondary voltages, primary and secondary turns and primary and secondary currents. The other three are calculated.
  3. The usual thing is to give the rating, both voltages and the turns of one winding. If you are not interested in the turns, leave those of the example: they do not change the currents.
Not every combination works: with the turns and both currents, for example, the rating or one voltage is missing. If you get “Leave empty the fields you want to calculate”, change one of the values.

Transformer formulas

In an ideal transformer, the voltage of each winding is proportional to its number of turns and the power going in is the power coming out, so the currents go the opposite way to the voltages:

m = U₁ / U₂ = N₁ / N₂ = I₂ / I₁

The rated current on each side comes from the apparent power of the transformer:

Single-phase: I = S / U   ·   Three-phase: I = S / (√3 · U)

Where S is the rating in VA, U the voltage in V (in three-phase, phase-to-phase) and I the current in A. The volts per turn is the voltage of a winding divided by its turns, and it is the same on the primary and on the secondary.

Advertisement

The connection changes the turns ratio

In a three-phase transformer each winding is connected in wye (Y) or in delta (D or Δ). The delta winding gets the full phase-to-phase voltage and the wye winding, the phase-to-neutral voltage (U/√3). That is why the turns ratio is not always the voltage ratio:

ConnectionPrimarySecondaryTurns ratioTypical use
DynDeltaWye with neutralN₁/N₂ = √3 · U₁/U₂Low-voltage distribution (Dyn11)
YynWyeWye with neutralN₁/N₂ = U₁/U₂Small transformers
DdDeltaDeltaN₁/N₂ = U₁/U₂Industry, no neutral
YdWyeDeltaN₁/N₂ = U₁/(√3 · U₂)Power station step-up transformers

The ratio of line currents is always the inverse of the ratio of line voltages: I₂/I₁ = U₁/U₂.

Worked example

Three-phase Dyn11 distribution transformer of 630 kVA, 20 kV / 400 V, with 20 turns in each secondary winding:

m = 20,000 / 400 = 50
I₁ = 630,000 / (√3 · 20,000) ≈ 18.19 A   ·   I₂ = 630,000 / (√3 · 400) ≈ 909.33 A
N₁ = √3 · 50 · 20 ≈ 1732 turns

Each secondary winding is in wye and sees 400/√3 ≈ 230.94 V, so the volts per turn are 230.94 / 20 ≈ 11.55 V. The delta primary sees 20,000 V with 1732 turns: 20,000 / 1732 ≈ 11.55 V, the same.

Rated currents of the most common transformers

Three-phase, with the secondary at 400 V phase-to-phase and the primary at 20 kV:

Rating (kVA)I₁ at 20 kV (A)I₂ at 400 V (A)
1002.89144.3
1604.62230.9
2507.22360.8
40011.55577.4
63018.19909.3
80023.091154.7
100028.871443.4
125036.081804.2
160046.192309.4
200057.742886.8
250072.173608.4

They are standard ratings (R10 series). To size the secondary protection and the breaking capacity of the circuit breaker, also look at the short-circuit current.

What it does not take into account

The calculator uses the ideal transformer. In a real one you have to add:

  • The voltage drop under load: because of the short-circuit voltage (4 % to 6 % in distribution), the secondary voltage drops a little under load. That is why many distribution transformers give 420 V at no load.
  • The losses in the iron (no load) and in the copper (under load), which are about 1 % to 2 % of the rating.
  • The tap changer positions (for example, ±2.5 % and ±5 %), which change the primary turns to adjust the voltage.
Advertisement

Frequently asked questions

What is the transformation ratio?

It is the quotient between the primary and the secondary voltage: m = U₁/U₂. In an ideal transformer it matches the turns ratio (N₁/N₂) and is the inverse of the current ratio (I₂/I₁): if the voltage drops 50 times, the current rises 50 times.

How do you calculate the rated current of a transformer?

By dividing the rating by the voltage: I = S/U in single-phase and I = S/(√3 · U) in three-phase, with the phase-to-phase voltage. A 630 kVA transformer at 400 V gives 630,000 / (1.732 · 400) ≈ 909 A on the secondary.

Why is the turns ratio of a Dyn transformer not the voltage ratio?

Because each winding does not see the same line voltage: the delta primary gets the full phase-to-phase voltage and the wye secondary, the phase-to-neutral voltage (U₂/√3). That is why N₁/N₂ = √3 · U₁/U₂. In Yyn and Dd both ratios are the same.

Do the turns change the power?

No. The power depends on the size of the core and the cross-section of the conductors. The turns only set the voltage ratio and the volts per turn, which grow with the transformer rating.

Is it valid for a real transformer?

Yes, for the rated values. It is the ideal transformer: it does not include the voltage drop under load or the losses, which in distribution transformers are about 1 % to 2 % at full load.