Electric motor calculator: current, power, voltage, power factor and efficiency

Calculate the current of a three-phase, single-phase or DC electric motor from its power, voltage, power factor and efficiency, or the missing value.

Fill in 4 of the 5 fields and the missing one is calculated. You can type in any of them.

The one on the nameplate: it is the mechanical power delivered by the shaft.
In three-phase, the phase-to-phase voltage.
—
%
The one on the nameplate. With 0 the torque is not calculated.
Input power from the grid—
Losses (lost as heat)—
Apparent power—
Shaft torque—

Use this calculator for reference only, as we cannot guarantee that the results are free of errors.

Disclaimer

https://dyaii.es/en/electric-motor-calculator/

Advertisement

With the nameplate data of an electric motor you know how much current it draws from the grid, how much power it takes in, how much is lost as heat and what torque it gives at the shaft. This calculator works for three-phase, single-phase and DC motors, and in both directions: from the power, the voltage, cos φ and the efficiency it gets the current, and with the measured current it gets the power, cos φ or the efficiency.

How to use the calculator

  1. Choose the motor type: three-phase, single-phase or DC. The usual voltage is filled in (400 V, 230 V or 24 V), which you can change.
  2. Enter all the values except one among output power, voltage, current, cos φ and efficiency. The one you leave empty is calculated. In DC there is no cos φ.
  3. If you want the torque, enter the nameplate speed in rpm (or in any other unit). With 0 it is not calculated.
  4. Every value accepts any unit: power in kW, CV or HP, voltage in V or kV, current in A or mA…

Motor power formulas

The nameplate power is the output power (P), the mechanical power delivered by the shaft. The power the motor takes from the grid, the input power (P₁), is higher because part of it is lost as heat: the ratio between the two is the efficiency η.

Three-phase: P = √3 · U · I · cos φ · η
Single-phase: P = U · I · cos φ · η
DC: P = U · I · η

With P in watts, U the voltage in volts (in three-phase, phase-to-phase), I the current in amperes, cos φ the power factor and η the efficiency as a fraction (90.4 % = 0.904). Solving for the current:

I = P / (√3 · U · cos φ · η)

The other results:

P₁ = P / η · Losses = P₁ − P · S = √3 · U · I (in single-phase, U · I)
Advertisement

Shaft torque

The torque is the output power divided by the angular speed:

M = P / ω, with ω = 2π · n / 60

With P in watts, n in rpm and M in N·m. With round numbers you get the workshop formula M (N·m) = 9550 · P (kW) / n (rpm).

Worked example

A 7.5 kW three-phase motor at 400 V, with cos φ = 0.82, 90.4 % efficiency and 1460 rpm (the default values in the calculator):

I = 7500 / (√3 · 400 · 0.82 · 0.904) = 7500 / 513.6 ≈ 14.60 A
P₁ = 7.5 / 0.904 ≈ 8.30 kW → losses ≈ 0.80 kW
S = √3 · 400 · 14.60 / 1000 ≈ 10.12 kVA
M = 7500 / (2π · 1460 / 60) ≈ 49.05 N·m

Current of three-phase motors at 400 V and IE2 and IE3 efficiencies

Approximate full-load current of 4-pole three-phase squirrel-cage motors at 400 V, from the table of standard currents in IEC 60947-4-1 (the one used by manufacturers of contactors and motor protection circuit breakers), and minimum efficiency at 50 Hz of classes IE2 and IE3 for 4-pole motors according to IEC 60034-30-1. Each real motor has its own values: the nameplate always prevails.

Power (kW)Current at 400 V (A)Minimum η IE2 (%)Minimum η IE3 (%)
0.751.979.682.5
1.12.781.484.1
1.53.682.885.3
2.24.984.386.7
36.585.587.7
48.586.688.6
5.511.587.789.6
7.515.588.790.4
112289.891.4
152990.692.1
18.53591.292.6
224191.693.0
305592.393.6
376692.793.9
458093.194.2
559793.594.6
7513294.095.0
9016094.295.2
11019594.595.4
13223094.795.6
16028094.995.8
20035095.196.0
In the European Union, Regulation (EU) 2019/1781 has required class IE3 for new motors from 0.75 to 1000 kW since July 2021, and IE4 for those from 75 to 200 kW since July 2023.

Which cos φ to use

The power factor of an induction motor is not set by any standard: it depends on the size, the number of poles and, above all, the load. As a guide, for 4-pole three-phase motors at full load:

  • Small motors, under 1.5 kW: 0.70 to 0.80.
  • Medium motors, from 2 to 30 kW: 0.80 to 0.86.
  • Large motors: 0.85 to 0.90.

At half load, cos φ drops quite a lot and the efficiency somewhat less; at no load, cos φ can fall below 0.3. An oversized motor consumes a lot of reactive energy.

Common mistakes

  • Forgetting the efficiency: with I = P / (√3 · U · cos φ) you get a lower current than the real one, because the nameplate power is the output, not the input.
  • Phase voltage instead of line voltage: in three-phase, U is the phase-to-phase voltage (400 V), not the phase-to-neutral one (230 V).
  • Mixing up CV and HP: 1 CV (metric horsepower) = 735.5 W and 1 HP = 745.7 W. The calculator accepts both.
  • Taking the starting current for the running current: with direct-on-line starting, a squirrel-cage motor draws 5 to 8 times the rated current for a few seconds. To choose the protection and the cable, follow ITC-BT-47 of Spain's low-voltage code (REBT): the conductors of a motor are sized for 125 % of its full-load current.
Advertisement

Frequently asked questions

What power is on a motor nameplate?

The output (mechanical) power delivered by the shaft at full load. The power drawn from the grid is higher: the output divided by the efficiency. That is why, to calculate the current, you have to take the efficiency into account as well as cos φ.

How do you calculate the current of a three-phase motor?

I = P / (√3 · U · cos φ · η), with P in watts, U the phase-to-phase voltage, cos φ the power factor and η the efficiency as a fraction. A 7.5 kW motor at 400 V with cos φ 0.82 and 90.4 % efficiency draws about 14.6 A.

What cos φ and efficiency do I enter if I do not have the nameplate?

For a 4-pole three-phase motor at full load, a cos φ of 0.8 to 0.86 and the minimum efficiency of its class (IE3 for new motors in Europe) give an approximate result. You have the tables in the explanation. Always better, the nameplate data.

How do you calculate the torque of a motor?

M = P / ω, the output power in watts divided by the angular speed in rad/s (ω = 2π · n / 60). In practice, M (N·m) = 9550 · P (kW) / n (rpm).

Is the starting current the same?

No. With direct-on-line starting, a squirrel-cage motor draws 5 to 8 times the rated current for a few seconds. This calculator gives the running current at the stated power.