Capacitor to run a three-phase motor on single-phase power
Size the capacitor to run a three-phase motor on single-phase power (Steinmetz connection): capacitance in µF from the motor power, or the other way.
A three-phase motor can run on a single-phase supply if you connect a capacitor that creates the third phase (Steinmetz connection). This calculator gives the capacitance from the motor power, the voltage and the frequency.
How to use the calculator
- Enter the motor power (the nameplate value), the supply voltage and the frequency.
- You get the capacitance in microfarads. If you type the capacitance, the motor power it can handle is calculated.
Capacitor formula
With P in watts, f in hertz and V in volts, C comes out in farads; times 10⁶, in microfarads (µF). At 230 V and 50 Hz that is about 60 µF per kW.
Worked example
A 1.5 kW motor at 230 V and 50 Hz:
Capacitor table at 230 V and 50 Hz
| Motor power (kW) | Capacitor (µF) |
|---|---|
| 0.18 | 11 |
| 0.25 | 15 |
| 0.37 | 22 |
| 0.55 | 33 |
| 0.75 | 45 |
| 1.1 | 66 |
| 1.5 | 90 |
| 2.2 | 132 |
| 3 | 181 |
How to wire it
- The motor must accept 230 V in delta (230/400 V nameplate) and be connected in delta.
- Line and neutral go to two motor terminals, and the capacitor links one of those terminals to the third.
- To reverse the rotation, move the capacitor to the other supply terminal.
Frequently asked questions
What voltage rating should the capacitor have?
At least 400 V working voltage for 230 V supplies, and it must be a motor capacitor (continuous duty).
Does it work for any motor?
For small motors, usually up to 2 or 3 kW. Above that, a variable frequency drive with single-phase input is a better choice.
Related calculators
- Battery life calculator (Ah, Wh and Peukert)
- Voltage drop calculator and wire size
- Delta to wye (Δ-Y) conversion calculator for resistors and impedances
- Power factor correction calculator: capacitor bank sizing in kVAR and µF
- Cable tray bend and offset calculator
- kW to amps calculator: three-phase, single-phase and DC current