Capacitor to run a three-phase motor on single-phase power

Size the capacitor to run a three-phase motor on single-phase power (Steinmetz connection): capacitance in µF from the motor power, or the other way.

Fill in 3 of the 4 fields and the missing one is calculated. You can type in any of them.

Use this calculator for reference only, as we cannot guarantee that the results are free of errors.

Disclaimer

https://dyaii.es/en/three-phase-motor-capacitor-calculator/

Advertisement

A three-phase motor can run on a single-phase supply if you connect a capacitor that creates the third phase (Steinmetz connection). This calculator gives the capacitance from the motor power, the voltage and the frequency.

How to use the calculator

  1. Enter the motor power (the nameplate value), the supply voltage and the frequency.
  2. You get the capacitance in microfarads. If you type the capacitance, the motor power it can handle is calculated.

Capacitor formula

C = P / (2π · f · V²)

With P in watts, f in hertz and V in volts, C comes out in farads; times 10⁶, in microfarads (µF). At 230 V and 50 Hz that is about 60 µF per kW.

Advertisement

Worked example

A 1.5 kW motor at 230 V and 50 Hz:

C = 1500 / (2π · 50 · 230²) ≈ 90 µF

Capacitor table at 230 V and 50 Hz

Motor power (kW)Capacitor (µF)
0.1811
0.2515
0.3722
0.5533
0.7545
1.166
1.590
2.2132
3181

How to wire it

  1. The motor must accept 230 V in delta (230/400 V nameplate) and be connected in delta.
  2. Line and neutral go to two motor terminals, and the capacitor links one of those terminals to the third.
  3. To reverse the rotation, move the capacitor to the other supply terminal.
The motor delivers between 60 and 70 % of its power and starts with little torque. For starting under load, a start capacitor 2 or 3 times larger is added and disconnected once the motor picks up speed.
Advertisement

Frequently asked questions

What voltage rating should the capacitor have?

At least 400 V working voltage for 230 V supplies, and it must be a motor capacitor (continuous duty).

Does it work for any motor?

For small motors, usually up to 2 or 3 kW. Above that, a variable frequency drive with single-phase input is a better choice.