Fire flow calculator: hose reels, hydrants, sprinklers and water reserve

Work out the flow of a hose reel, hydrant or sprinkler from its K factor and pressure, the total flow of the outlets running together and the reserve tank for the duration.

Fill in 0 of the 1 fields and the missing one is calculated. You can type in any of them.

Advanced options (4)

They come with a typical value: change it only if you know it.

Given by the manufacturer on the nozzle or sprinkler. Sprinklers: K57, K80, K115…
L/min/√bar
Total flow—
Total flow in L/min—
Water reserve—
Discharge density (12 m² sprinklers)—

Use this calculator for reference only, as we cannot guarantee that the results are free of errors.

Disclaimer

https://dyaii.es/en/fire-flow-calculator/

Advertisement

A water-based fire protection system (hose reels, hydrants or sprinklers) has to deliver a minimum flow, at a minimum pressure, for a given time. That sizes the pump and the reserve tank. The calculator gives the flow of each outlet from its K factor, the total flow of those running at the same time and the water to be stored. It is a preliminary sizing: the hydraulic design is done by a qualified installer.

Formulas

q = K · √P  ·  Q = n · q  ·  V = Q · t

q is the flow of one outlet in L/min, K its factor (marked on the nozzle or sprinkler) and P the residual pressure in bar at the outlet. n is the number of outlets the standard assumes running at once and t the duration. Example: 2 hose reels of 25 mm with K 68 at 2 bar give 2 · 96 = 192 L/min, and for 1 hour need 11.5 m³ of reserve.

Reference values

SystemOutlets at oncePressureFlow per outletDuration
25 mm hose reel2 (the most remote)2 to 5 bar≈ 1.6 L/s (96 L/min)1 h
45 mm hose (lay-flat)22 to 5 bar≈ 3.3 L/s (200 L/min)1 h
Hydrants2≥ 1 bar500 to 1,000 L/min depending on risk30 to 90 min
Sprinklers OH2 (EN 12845)144 m² area (12 at 12 m²)≥ 0.35 bar5 mm/min · 12 m² = 60 L/min60 min

These are guide values: the number of outlets, the hazard class and the duration are set by the applicable standard for the building use and risk level.

Advertisement

Several ways to get each value

  • The flow of an outlet from its K and the pressure.
  • The pressure needed for a flow: enter the flow and clear the pressure. A K80 sprinkler that must give 60 L/min needs (60/80)² = 0.56 bar.
  • The K factor of an unknown nozzle, by measuring the flow (filling a drum) and the pressure with a Pitot gauge.
  • The reserve for another duration: change the time.

What the full design adds

  • The pressure losses in the pipework to the most remote outlet, added to the outlet pressure: pressure loss calculator.
  • The static head and the pressure the pump set must deliver: pump power.
  • If several systems must run at once, their flows and reserves are added.
Advertisement

Frequently asked questions

What flow does a 25 mm hose reel give?

With a K 68 nozzle at 2 bar, q = 68 · √2 = 96 L/min (1.6 L/s). Two at once, 192 L/min, and for one hour you need 11.5 m³ of reserve.

What is the K factor?

The constant of a nozzle or sprinkler linking flow and pressure: q = K · √P, with q in L/min and P in bar. A K80 sprinkler at 1 bar discharges 80 L/min; at 4 bar, twice that.

How is a fire water tank sized?

Flow of the outlets running at once times the duration required by the standard: V = n · q · t. If several systems (hose reels and hydrants) must run together, add them.

What pressure must a hose reel have?

Typically at least 2 bar residual pressure at the two most remote hose reels for one hour, and no more than 5 bar at the nozzle so it can be handled.

Related calculators

Share

WhatsApp X LinkedIn Telegram Email
Advertisement

Install Diseño y automatización de instalaciones industriales on your phone

All the calculators one tap away, full screen, like an app. It takes no space and is always up to date.