Fire flow calculator: hose reels, hydrants, sprinklers and water reserve
Work out the flow of a hose reel, hydrant or sprinkler from its K factor and pressure, the total flow of the outlets running together and the reserve tank for the duration.
A water-based fire protection system (hose reels, hydrants or sprinklers) has to deliver a minimum flow, at a minimum pressure, for a given time. That sizes the pump and the reserve tank. The calculator gives the flow of each outlet from its K factor, the total flow of those running at the same time and the water to be stored. It is a preliminary sizing: the hydraulic design is done by a qualified installer.
Formulas
q is the flow of one outlet in L/min, K its factor (marked on the nozzle or sprinkler) and P the residual pressure in bar at the outlet. n is the number of outlets the standard assumes running at once and t the duration. Example: 2 hose reels of 25 mm with K 68 at 2 bar give 2 · 96 = 192 L/min, and for 1 hour need 11.5 m³ of reserve.
Reference values
| System | Outlets at once | Pressure | Flow per outlet | Duration |
|---|---|---|---|---|
| 25 mm hose reel | 2 (the most remote) | 2 to 5 bar | ≈ 1.6 L/s (96 L/min) | 1 h |
| 45 mm hose (lay-flat) | 2 | 2 to 5 bar | ≈ 3.3 L/s (200 L/min) | 1 h |
| Hydrants | 2 | ≥ 1 bar | 500 to 1,000 L/min depending on risk | 30 to 90 min |
| Sprinklers OH2 (EN 12845) | 144 m² area (12 at 12 m²) | ≥ 0.35 bar | 5 mm/min · 12 m² = 60 L/min | 60 min |
These are guide values: the number of outlets, the hazard class and the duration are set by the applicable standard for the building use and risk level.
Several ways to get each value
- The flow of an outlet from its K and the pressure.
- The pressure needed for a flow: enter the flow and clear the pressure. A K80 sprinkler that must give 60 L/min needs (60/80)² = 0.56 bar.
- The K factor of an unknown nozzle, by measuring the flow (filling a drum) and the pressure with a Pitot gauge.
- The reserve for another duration: change the time.
What the full design adds
- The pressure losses in the pipework to the most remote outlet, added to the outlet pressure: pressure loss calculator.
- The static head and the pressure the pump set must deliver: pump power.
- If several systems must run at once, their flows and reserves are added.
Frequently asked questions
What flow does a 25 mm hose reel give?
With a K 68 nozzle at 2 bar, q = 68 · √2 = 96 L/min (1.6 L/s). Two at once, 192 L/min, and for one hour you need 11.5 m³ of reserve.
What is the K factor?
The constant of a nozzle or sprinkler linking flow and pressure: q = K · √P, with q in L/min and P in bar. A K80 sprinkler at 1 bar discharges 80 L/min; at 4 bar, twice that.
How is a fire water tank sized?
Flow of the outlets running at once times the duration required by the standard: V = n · q · t. If several systems (hose reels and hydrants) must run together, add them.
What pressure must a hose reel have?
Typically at least 2 bar residual pressure at the two most remote hose reels for one hour, and no more than 5 bar at the nozzle so it can be handled.