Steam consumption calculator (kg/h to kW)
Calculate the heat output of a saturated steam flow as it condenses (kg/h to kW) or the steam used by equipment of a given power, with the steam volume at its pressure.
Saturated steam carries its energy mostly as latent heat: the heat it releases when it condenses in a heat exchanger, a jacketed kettle or a coil. With this calculator you convert kg/h of steam to kW and back, to know which boiler you need, how much steam a piece of equipment uses or how much power a steam flow gives you. It also tells you the volume it takes up at its pressure, so you can choose the pipe.
How to use the calculator
- Enter the steam pressure (gauge, the one on the pressure gauge).
- Enter the steam flow rate to get the power, or the equipment power to get the steam it uses.
Steam consumption formula
Where P is the power (kW), ṁ the steam flow rate (kg/s) and hfg the latent heat of vaporisation at the steam pressure (kJ/kg), taken from the saturated steam table. With the flow rate in kg/h:
The steam volume is ṁ · vg, where vg is the specific volume of steam at that pressure (m³/kg).
Worked example
1000 kg/h of saturated steam at 5 bar gauge (158.9 °C, hfg ≈ 2085 kJ/kg):
It takes up about 315 m³/h (vg ≈ 0.315 m³/kg): at 25 m/s you would need a pipe with an inside diameter of about 67 mm, a DN 65.
Latent heat by pressure
| Pressure (bar g) | Temperature (°C) | hfg (kJ/kg) | Steam per kW (kg/h) |
|---|---|---|---|
| 0 | 100 | 2257 | 1.60 |
| 1 | 120.4 | 2201 | 1.64 |
| 3 | 143.8 | 2133 | 1.69 |
| 5 | 158.9 | 2085 | 1.73 |
| 8 | 175.4 | 2030 | 1.77 |
| 10 | 184.1 | 2000 | 1.80 |
Source: DYAII saturated steam table (the same one used by the steam calculator).
Frequently asked questions
How many kg of steam is 1 kW?
Between 1.5 and 1.8 kg/h depending on the pressure: at 0 bar (100 °C) 1.6 kg/h and at 10 bar about 1.8 kg/h, because the latent heat falls as the pressure rises.
Why is only the latent heat counted?
Because it is the heat the steam releases when it condenses in the equipment, and the condensate leaves at almost the same temperature. If the condensate cools further inside the equipment, the real power is slightly higher.
What is a boiler horsepower?
An old measure of a boiler’s output: 15.65 kg/h of steam “from and at 100 °C”, about 9.81 kW.