Total harmonic distortion (THD) and K-factor

Work out the total harmonic distortion (THD) of a current or voltage from its fundamental and harmonics 3 to 13, the true rms value with harmonics and the transformer K-factor.

Fill in 7 of the 8 fields and the missing one is calculated. You can type in any of them.

Amps, volts or % of the fundamental (enter 100): all in the same unit, as the power analyser gives them.
—
—
—
—
—
—
—
%
THD relative to total rms (THD-R)—
Total rms value with harmonics—
Rms value of the harmonics—
K-factor (to choose the transformer)—
Distortion factor (maximum achievable power factor: 1 / √(1 + THD²))—

Use this calculator for reference only, as we cannot guarantee that the results are free of errors.

Disclaimer

https://dyaii.es/en/thd-calculator/

Advertisement

Variable frequency drives, power supplies, LEDs and UPSs do not draw a sinusoidal current: they draw it in pulses. That distorted current can be broken down into the 50 Hz wave (the fundamental) plus waves at multiple frequencies, the harmonics: the 3rd at 150 Hz, the 5th at 250 Hz… Total harmonic distortion (THD) sums up in one number how far the wave departs from a sine.

THD formula

THD = √(X₃² + X₅² + X₇² + … ) / X₁ · 100

X₁ is the rms value of the fundamental and Xh that of each harmonic, all in the same unit (amps, volts or % of the fundamental). Example: a six-pulse drive with 2 % 3rd, 30 % 5th, 15 % 7th, 1 % 9th, 7 % 11th and 5 % 13th: THD = √(4 + 900 + 225 + 1 + 49 + 25) = 34.7 %.

LoadMain harmonicsTypical current THD
6-pulse drive without filter5th, 7th, 11th, 13th30 to 80 %
Drive with line reactor5th, 7th30 to 45 %
12-pulse rectifier11th, 13th10 to 15 %
Single-phase supplies, LEDs, computers3rd, 5th80 to 150 %

True rms value and THD-R

X = √(X₁² + Σ Xh²) = X₁ · √(1 + THD²)  ·  THD-R = √(Σ Xh²) / X

Harmonics raise the rms value: with 34.7 % THD, 100 A of fundamental is 105.8 A true rms, and that is what heats cables and breakers. THD-R refers to the total rms value and never exceeds 100 %; standards use THD-F, the formula above.

Advertisement

Transformer K-factor

K = Σ (Xh · h)² / Σ Xh²

A transformer's eddy-current losses grow with the square of frequency, so high harmonics heat much more. The K-factor (UL 1561, IEEE C57.110) tells how many times: the example gives 4.8, so a K-13 transformer is needed (the next standard value above: 4, 9, 13, 20…).

Limits and several ways to get each value

  • Public network voltage: EN 50160, THD up to 8 %; IEEE 519, under 5 % up to 1 kV.
  • Equipment current: IEC 61000-3-2 (up to 16 A per phase) and 61000-3-12 (16 to 75 A).
  • The largest harmonic you can allow for a given THD: enter the THD and leave that harmonic empty.
  • The fundamental if you only know the harmonics in amps and the analyser's THD.
Advertisement

Frequently asked questions

How is THD calculated?

THD = √(X₂² + X₃² + … ) / X₁ · 100, with X₁ the fundamental and Xh each harmonic. A drive with 30 % 5th, 15 % 7th, 7 % 11th and 5 % 13th (plus some 3rd and 9th): THD = √(4 + 900 + 225 + 1 + 49 + 25) = 34.7 %.

What is the difference between THD-F and THD-R?

THD-F divides by the fundamental and can exceed 100 %; THD-R divides by the total rms value and never reaches 100 %. Standards (IEC 61000, IEEE 519) use THD-F; some analysers show the other.

What voltage THD is allowed?

EN 50160 sets up to 8 % voltage THD (harmonics up to the 40th) for the public LV network, and IEEE 519 recommends under 5 % at the point of connection up to 1 kV.

What is the K-factor?

K = Σ (Ih · h)² / Σ Ih²: how much more harmonics heat a transformer than a sinusoidal current of the same rms value. For drive and computer loads, K-4, K-13 or K-20 transformers are chosen.