Skip to content
EN
  • Español
  • English
Advertisement

Power factor correction calculator: capacitor bank sizing in kVAR and µF

Size the capacitor bank to improve your power factor: kVAR, µF per capacitor in delta or wye, current before and after, and the kVA you save.

Fill in 3 of the 4 fields and the missing one is calculated. You can type in any of them.

In three-phase systems, the line-to-line voltage (400 V in Spain).
—
Usually 0.95 or higher: below that, the utility charges for reactive energy.
—
Many capacitors are built for 440 V or more: at 400 V they deliver less power than their nameplate says.
Capacitance of each capacitor (C)—
Nameplate rating to order (at Un and fn)—
Current before correction—
Current after correction—
Apparent power saved—
Capacitor bank current—
Apparent power before (S₁)—
Apparent power after (S₂)—
Reactive power before (Q₁)—
Remaining reactive power (Q₂)—

Use this calculator for reference only, as we cannot guarantee that the results are free of errors.

Disclaimer

https://dyaii.es/en/power-factor-correction-calculator/

Advertisement

Motors, transformers and fluorescent lamps draw reactive energy: it does no work, but it loads the cables and the bill. A capacitor bank supplies it inside the installation itself and raises the power factor (cos φ). This calculator tells you how many kVAR you need, the capacitance in µF of each capacitor in delta, in wye or single-phase, and how much the current and the apparent power drop. It also works backwards: with a bank you already have, the cos φ you reach.

How to use the calculator

  1. Choose the capacitor connection: the usual voltage is filled in automatically (400 V three-phase, 230 V single-phase). Check the frequency (50 Hz in Europe, 60 Hz in the Americas).
  2. Enter the active power of the installation and its present power factor (you will find it on the bill or on the power analyzer).
  3. Enter the target cos φ (0.95 or higher) and you get the capacitor bank rating. If you enter the bank rating, the cos φ you reach is calculated; and if you leave the active power empty, the power that bank can compensate.
  4. If you are going to buy capacitors with a different voltage rating (440 V, for example), choose “Another rated voltage”: you will see the nameplate rating you need to order.

Capacitor bank formula

Qc = P · (tan φ₁ − tan φ₂)

Where Qc is the reactive power of the bank (kVAR), P the active power (kW), φ₁ the angle at the present cos φ and φ₂ the angle at the target cos φ. From the cosine, the tangent is tan φ = √(1 − cos² φ) / cos φ.

The bank does not change the active power: it only subtracts reactive power. The reactive power goes from Q₁ = P · tan φ₁ to Q₂ = P · tan φ₂, and the apparent power from S₁ = P / cos φ₁ to S₂ = P / cos φ₂.

Advertisement

Capacitance of each capacitor

With ω = 2π · f and U the line-to-line voltage (three-phase) or the supply voltage (single-phase):

ConnectionVoltage across each capacitorCapacitance of each one
Three-phase, delta (3 capacitors)UC = Qc / (3 · ω · U²)
Three-phase, wye (3 capacitors)U / √3C = Qc / (ω · U²)
Single-phase (1 capacitor)UC = Qc / (ω · U²)
In wye each capacitor needs three times the capacitance it needs in delta to deliver the same power, because it only sees U / √3. That is why three-phase banks are almost always delta-connected.

Current before and after

I = P / (√3 · U · cos φ) three-phase · I = P / (U · cos φ) single-phase

As cos φ rises, the current drawn from the supply drops for the same active power. The bank draws its own current, Ic = Qc / (√3 · U) in three-phase, which is the one to use when sizing its cables and protective devices.

Capacitors with a different rated voltage

The power of a capacitor grows with the square of the voltage and with the frequency. A capacitor with rated power Qn at Un and fn delivers, on a supply of voltage U and frequency f:

Q = Qn · (U / Un)² · f / fn

For example, a 50 kVAR capacitor rated at 440 V delivers about 41.3 kVAR at 400 V. To get Qc on your supply you have to order Qn = Qc · (Un / U)² · fn / f. Low-voltage capacitors follow the standard UNE-EN 60831-1.

kVAR per kW table

Multiply the active power (kW) by the number in the table and you get the kVAR of the bank (it is tan φ₁ − tan φ₂):

Present cos φto 0.90to 0.95to 0.98to 1
0.600.8491.0051.1301.333
0.650.6850.8400.9661.169
0.700.5360.6920.8171.020
0.750.3980.5530.6790.882
0.800.2660.4210.5470.750
0.850.1350.2910.4170.620
0.90—0.1560.2810.484

Worked example

A plant with 100 kW at 400 V and 50 Hz has cos φ = 0.75 and the goal is 0.95 with a delta-connected bank:

tan φ₁ = √(1 − 0.75²) / 0.75 = 0.8819 · tan φ₂ = √(1 − 0.95²) / 0.95 = 0.3287
Qc = 100 · (0.8819 − 0.3287) ≈ 55.32 kVAR
C = 55,323 / (3 · 2π · 50 · 400²) ≈ 366.87 µF per capacitor

The current drops from 100,000 / (√3 · 400 · 0.75) ≈ 192.45 A to 100,000 / (√3 · 400 · 0.95) ≈ 151.93 A, and the apparent power from 133.33 kVA to 105.26 kVA: a saving of 28.07 kVA. If the capacitors are rated at 440 V, you have to order 55.32 · (440 / 400)² ≈ 66.94 kVAR on the nameplate.

Tips for choosing the capacitor bank

  • Aim for a cos φ between 0.95 and 0.98. Reaching 1 takes a much bigger bank for very little gain and, if the load drops, the installation becomes capacitive.
  • If the load changes during the day, use an automatic bank with steps (for example, 5 + 10 + 20 + 20 kVAR) and a controller that switches in only the ones needed.
  • With variable frequency drives or other loads that generate harmonics, the capacitors can go into resonance with the transformer: use capacitors with a higher voltage rating and detuning reactors.
  • In Spain, for supplies above 15 kW the utility bills the reactive energy that exceeds 33 % of the active energy, which is exactly what happens with a cos φ below 0.95.
Advertisement

Frequently asked questions

How many kVAR do I need to go from a power factor of 0.75 to 0.95?

About 0.553 kVAR per kW of active power: tan φ₁ − tan φ₂ = 0.882 − 0.329. For a 100 kW installation, a capacitor bank of about 55 kVAR.

What is the difference between connecting the capacitors in delta or in wye?

In delta each capacitor sees the line-to-line voltage and needs three times less capacitance than in wye for the same power. That is why almost all three-phase capacitor banks are delta-connected.

Can I use 440 V capacitors on a 400 V supply?

Yes, and it is common practice because they withstand harmonics and overvoltages better, but they deliver less power: Q = Qn · (U / Un)². A 50 kVAR capacitor rated at 440 V delivers about 41.3 kVAR at 400 V. Choose “Another rated voltage” and the calculator tells you the nameplate rating to order.

What happens if I install too many capacitors?

The installation becomes capacitive (overcompensated): the voltage rises, the current grows again and the utility may also penalize capacitive reactive energy. That is why automatic capacitor banks switch in only the steps that are needed.

How much do I save by compensating reactive energy?

You stop paying the reactive energy surcharge on your bill and the current drops: cables, transformer and protective devices have more headroom and there are fewer heat losses. The active energy (kWh) your machines use stays the same.

Related calculators

Share

WhatsApp X LinkedIn Telegram Email
Advertisement

Install Diseño y automatización de instalaciones industriales on your phone

All the calculators one tap away, full screen, like an app. It takes no space and is always up to date.