Voltage drop calculator and wire size

Calculate the voltage drop of a cable in three-phase, single-phase or DC, the minimum wire size under Spain's REBT limits and the maximum length.

Fill in 2 of the 4 fields and the rest are calculated. You can type in any of them.

In three-phase, the phase-to-phase voltage.
—
The operating temperature of the insulation (the worst case). 20 °C, for a cold cable or a light load.
From the source to the load (one way).
Type the drop in V or in %, not both.
%
Filled in with the limit. If you type another value, the limit changes to “Other”.
%
About 0.08 Ω/km in low-voltage cables. Enter 0 to ignore it.
Load current—
Voltage at the load—
Minimum cross-section for the limit—
Proposed standard size—
Drop with the standard size—
Maximum length with this cross-section—
Conductor resistivity—
Resistance of one conductor—
Power lost in the cable—

Use this calculator for reference only, as we cannot guarantee that the results are free of errors.

Disclaimer

https://dyaii.es/en/voltage-drop-calculator/

Advertisement

Every cable has resistance: when current flows, part of the voltage is lost along the way and the load gets a little less than there is at the source. That loss is the voltage drop, and Spain's low-voltage electrical code (Reglamento Electrotécnico para Baja Tensión, REBT) limits it. This calculator gives you the drop of a three-phase, single-phase or DC line, in volts and as a percentage, the minimum cross-section of the cable with the standard size that meets it, or the maximum length the line can have without exceeding the limit.

How to use the calculator

  1. Choose the type of current: the usual voltage is filled in (400 V, 230 V or 24 V). Change it if yours is different.
  2. Choose the load data: the current, or the active power (with cos φ, the calculator works out the current).
  3. Choose the conductor (copper or aluminum) and its temperature: 70 °C for PVC cables and 90 °C for XLPE or EPR cables.
  4. Of these values, enter two: length, cross-section and voltage drop (in V or in %). The others are calculated. Length and cross-section give the drop; length and drop give the cross-section; cross-section and drop give the length.
  5. Choose the REBT limit that applies to your line (or type another one). Below you always get the minimum cross-section for that limit, the standard size that meets it and the maximum length with the cross-section you entered. The drawing warns in red if the drop exceeds the limit.

Voltage drop formula

In a balanced three-phase system (phase-to-phase drop):

ΔU = √3 · L · I · (R · cos φ + X · sin φ)

In single-phase (the current goes out on the phase and returns on the neutral: the length counts twice):

ΔU = 2 · L · I · (R · cos φ + X · sin φ)

In DC there is no reactance and no cos φ:

ΔU = 2 · L · I · R

Where L is the length of the line (one way), I the current, R = ρ / S the resistance of the conductor per unit length (resistivity divided by cross-section) and X its reactance, about 0.08 Ω/km in low-voltage cables. As a percentage:

ΔU (%) = ΔU / U · 100

If you give the power instead of the current: I = P / (√3 · U · cos φ) in three-phase, I = P / (U · cos φ) in single-phase and I = P / U in DC. Solving the formula for the cross-section:

S = ρ · cos φ / ( ΔU / (k · L · I) − X · sin φ ) · · · k = √3 or 2

If the reactance term is already larger than the drop you ask for, no cross-section can achieve it: you have to shorten the line, run cables in parallel or raise the voltage.

Advertisement

Resistivity of copper and aluminum

Metal conducts worse when hot. That is why the drop is calculated with the conductor at its maximum operating temperature, which depends on the insulation: 70 °C for PVC and 90 °C for XLPE and EPR. The calculator uses the conductivities in the REBT Technical Application Guide (Guía Técnica de Aplicación, annex 2, calculation of voltage drops):

Conductor20 °C70 °C (PVC)90 °C (XLPE, EPR)
Copper: conductivity γ (m/(Ω·mm²))564844
Copper: resistivity ρ (Ω·mm²/m)0.01790.02080.0227
Aluminum: conductivity γ (m/(Ω·mm²))353028
Aluminum: resistivity ρ (Ω·mm²/m)0.02860.03330.0357

Maximum voltage drop under the REBT

The REBT splits the voltage drop among the sections of the installation. These are the limits in each of its technical instructions (ITC-BT):

SectionInstructionMaximum drop
Main supply line (línea general de alimentación), all meters in one placeITC-BT-140.5 %
Main supply line, partial meter banksITC-BT-141 %
Individual branch line (derivación individual), meters grouped in more than one placeITC-BT-150.5 %
Individual branch line, all meters in one placeITC-BT-151 %
Individual branch line of a single user (no main supply line)ITC-BT-151.5 %
Indoor installation of dwellingsITC-BT-193 %
Other indoor installations: lightingITC-BT-193 %
Other indoor installations: other usesITC-BT-195 %
Industrial plants with their own transformer: lightingITC-BT-194.5 %
Industrial plants with their own transformer: other usesITC-BT-196.5 %

The ITC-BT-19 limits are counted from the origin of the indoor installation to any point of use: if a circuit hangs from a sub-panel, add the drop of the sub-panel feeder and that of the circuit. In industrial plants supplied at high voltage with their own transformer, the origin is the transformer output.

Standard cable sizes

The cross-section that comes out of the calculation is almost never one that is manufactured: you choose the next standard size up. These are the standard cross-sections (mm²) the calculator proposes:

1.52.54610162535
507095120150185240300

Above 300 mm², several cables are usually run in parallel: each carries its share of the current.

Worked example

A 400 V three-phase line feeds a 32 A motor with cos φ = 0.85, 50 m from the panel, through a 6 mm² copper cable with PVC insulation (70 °C, ρ = 1/48 Ω·mm²/m) and X = 0.08 Ω/km. With cos φ = 0.85, sin φ = 0.527:

R = 0.02083 / 6 = 0.003472 Ω/m · · · R · cos φ + X · sin φ = 0.002951 + 0.000042 = 0.002994 Ω/m
ΔU = √3 · 50 · 32 · 0.002994 ≈ 8.30 V · · · ΔU (%) = 8.30 / 400 · 100 ≈ 2.07 %

It is below the 5 % of ITC-BT-19 for uses other than lighting. The minimum cross-section for that 5 % (20 V) would be 2.47 mm²: the standard size is 2.5 mm², with which the drop is 4.94 %. And with 6 mm² the line could reach about 120 m without exceeding 5 %.

This calculator only looks at voltage drop. The final cross-section must also meet the current-carrying capacity of the cable for its installation method (ITC-BT-19 and UNE-HD 60364-5-52), the protection against overloads and short circuits (ITC-BT-22) and the minimum cross-sections for each type of circuit (ITC-BT-25 in dwellings).
Advertisement

Frequently asked questions

What is the maximum voltage drop allowed by Spain's REBT?

In indoor installations (ITC-BT-19), 3 % in dwellings and in lighting and 5 % in other uses, counted from the origin of the installation. The individual branch line has its own limit (1.5 %, 1 % or 0.5 %, ITC-BT-15) and the main supply line, 1 % or 0.5 % (ITC-BT-14).

Why do you multiply by 2 in single-phase and by √3 in three-phase?

In single-phase and in DC the current goes out along one conductor and returns along another: the drop is that of both (2 · L). In a balanced three-phase system there is no return through the neutral and the phase-to-phase drop is √3 times that of one conductor.

Which conductor temperature should I choose?

The maximum operating temperature of the insulation: 70 °C for PVC cables and 90 °C for XLPE or EPR cables. It is the worst case, because copper and aluminum conduct worse when hot. 20 °C is only valid for very lightly loaded cables.

Is voltage drop enough to choose the wire size?

No. The cross-section must also meet the current-carrying capacity of the cable for its installation method (ITC-BT-19 and UNE-HD 60364-5-52) and be protected by the circuit breaker or the fuse. You choose the largest of the cross-sections given by each criterion.

Do I need the cable reactance?

In small cross-sections it hardly matters, because the resistance is much larger. From about 95 mm², or with a low cos φ, the reactance (about 0.08 Ω/km) already weighs on the result. In DC it does not exist.