AWG to mm² converter: wire gauge, cross-section and diameter

Convert an AWG wire gauge to mm² and diameter, or the other way around, from 4/0 to AWG 40, and get the nearest standard metric size. With a full chart.

Fill in 1 of the 3 fields and the rest are calculated. You can type in any of them.

Filled in from the gauge. 1/0 = 0, 2/0 = −1, 3/0 = −2 and 4/0 = −3.
AWG
Of the solid conductor, without insulation.
Nearest whole AWG gauge (0 = 1/0, −1 = 2/0…)—
Nearest standard metric size—
Difference from the nearest metric size—
Metric size that is not too small—
Cross-section in kcmil (MCM)—
Copper resistance at 20 °C—

Use this calculator for reference only, as we cannot guarantee that the results are free of errors.

Disclaimer

https://dyaii.es/en/awg-to-mm2/

Advertisement

AWG (American Wire Gauge) is the way wires are sized in the United States and Canada, and the one you find on a lot of equipment, power supplies, data cables and American datasheets. In Europe cables are sized by their cross-section in mm². With this converter you turn an AWG gauge into mm² and diameter, or the other way around, and it tells you which standard metric size matches it.

How to use the converter

  1. Choose the AWG gauge from the list (4/0 to 40): the AWG number is filled in and you get the cross-section and the diameter.
  2. Or enter the cross-section or the diameter (in the unit you want) and you get the AWG number, with decimals if it falls between two gauges.
  3. Below you get the nearest whole gauge, the nearest standard metric size, the one that is not too small, the cross-section in kcmil and the copper resistance.
  4. In the drawing, the AWG conductor and the nearest metric one are at the same scale.

AWG gauge formula

The AWG scale (ASTM B258) goes from 4/0, the thickest, with a diameter of 0.46 inches (11.684 mm), to AWG 36, with 0.005 inches (0.127 mm), in 39 steps of equal ratio. From that you get:

d = 0.127 mm · 92(36 − n) / 39
S = π · d² / 4 · · · n = 36 − 39 · log₉₂(d / 0.127 mm)

Where n is the AWG number. Gauges thicker than 1 are written 1/0, 2/0, 3/0 and 4/0 (or 0, 00, 000 and 0000) and in the formula they are n = 0, −1, −2 and −3. Two easy rules: every 6 numbers the diameter is halved, and every 3 numbers, the cross-section.

Advertisement

AWG to mm² chart

AWGDiameter (mm)Cross-section (mm²)Nearest metric (mm²)
4/011.68107.2295
3/010.4085.0395
2/09.26667.4370
1/08.25153.4850
17.34842.4135
26.54433.6335
35.82726.6725
45.18921.1525
54.62116.7716
64.11513.3016
73.66510.5510
83.2648.36610
92.9066.6346
102.5885.2616
112.3054.1724
122.0533.3094
131.8282.6242.5
141.6282.0812.5
151.4501.6501.5
161.2911.3091.5
171.1501.0381
181.0240.8230.75
190.9120.6530.75
200.8120.5180.5
210.7230.4100.34
220.6440.3260.34
230.5730.2580.25
240.5110.2050.25
250.4550.1620.14
260.4050.1290.14
270.3610.1020.14
280.3210.08100.14
290.2860.0642—
300.2550.0509—
310.2270.0404—
320.2020.0320—
330.1800.0254—
340.1600.0201—
350.1430.0160—
360.1270.0127—
370.1130.0100—
380.1010.0080—
390.08970.0063—
400.07990.0050—

The metric sizes are those of IEC 60228 (from 0.5 mm²) and, below that, those of control cables (0.14, 0.25 and 0.34 mm²). From AWG 29 onwards there is no close metric size.

Above 4/0: kcmil

Cables thicker than 4/0 no longer have an AWG number: they are measured in kcmil (or MCM), thousands of circular mils. A circular mil is the area of a circle one thousandth of an inch in diameter:

1 kcmil = 0.5067 mm² · · · 4/0 = 211.6 kcmil = 107.2 mm²

The most common are 250, 300, 350, 500, 750 and 1000 kcmil (127, 152, 177, 253, 380 and 507 mm²).

Worked example

An American datasheet calls for 12 AWG wire. With n = 12:

d = 0.127 · 92(36 − 12) / 39 = 0.127 · 920.615 ≈ 2.053 mm · · · S = π · 2.053² / 4 ≈ 3.31 mm²

The nearest metric size is 4 mm²; 2.5 mm² falls short. And the other way around: a 2.5 mm² wire has a diameter of 1.784 mm and gives n ≈ 13.2, between AWG 13 (2.63 mm²) and AWG 14 (2.08 mm²).

When replacing an AWG cable with a metric one, choose an equal or larger size and check the ampacity and the voltage drop with the metric size, as required by Spain's low-voltage code (REBT).
Advertisement

Frequently asked questions

How many mm² is a 12 AWG wire?

A 12 AWG wire has 3.31 mm² and a diameter of 2.05 mm. The nearest standard metric size is 4 mm²; 2.5 mm² falls somewhat short.

Why is the wire thinner the higher the AWG number?

Because the number comes from the drawing passes: every time the wire goes through a die it gets thinner. An AWG 40 wire has been through many more passes than an AWG 10. Every 6 numbers the diameter is halved, and every 3, the cross-section.

What are 1/0, 2/0, 3/0 and 4/0?

The gauges thicker than AWG 1: 1/0 (or 0), 2/0 (00), 3/0 (000) and 4/0 (0000). In the formula they are n = 0, −1, −2 and −3. Above 4/0 (107.2 mm²) cables are measured in kcmil or MCM: thousands of circular mils.

Can I replace an AWG cable with a metric one?

Yes, choosing a metric size equal or larger (the one that is “not too small”) and checking the ampacity and the voltage drop with the metric size. AWG and metric sizes do not match exactly.

Does AWG apply to stranded cables?

Yes: the gauge of a stranded cable is that of a solid conductor with the same cross-section of metal. Its outside diameter is slightly larger because of the gaps between strands.