Wire resistance calculator: resistivity, length and cross-section
Calculate the resistance of a wire or conductor from its material, length, cross-section and temperature. Also solves for the length or the wire size.
Every conductor has resistance: more the longer it is, less the thicker it is, and it depends on the material and the temperature. This calculator gives you the resistance of a cable or a wire made of copper, aluminum, nichrome or any other material, corrected to its operating temperature, and also the other way around: what length or what cross-section gives a certain resistance. It is the first step in calculating the voltage drop and the losses of a line.
How to use the calculator
- Choose the material: its resistivity at 20 °C and its temperature coefficient are filled in. If it is not listed, choose “Other” and type the manufacturer's data.
- Enter the temperature of the conductor. At 20 °C the table resistivity is used as is; for a cable under load, use the operating temperature (70 °C with PVC, 90 °C with XLPE).
- Of length, cross-section and resistance, enter two: the third is calculated. Each one in the unit you want (m, km, ft; mm², cm², in²; mΩ, Ω…).
- In the drawing, the cable takes the color of the material, gets longer and thicker with the length and the cross-section, and the thermometer shows the temperature.
Wire resistance formula
Where R is the resistance (Ω), ρ the resistivity of the material (Ω·mm²/m), L the length (m) and S the cross-section (mm²). It is sometimes called Ohm's second law. In SI units the resistivity is in Ω·m and the cross-section in m² (1 Ω·mm²/m = 10⁻⁶ Ω·m). Solving for the others:
The reciprocal of resistivity is conductivity, σ = 1 / ρ, in S/m (or in m/(Ω·mm²), which is the same as MS/m). Copper has 58 MS/m.
Temperature correction
The resistivity of metals rises with temperature. Between about −50 °C and 200 °C it is corrected with a straight line:
Where ρ₂₀ is the resistivity at 20 °C, α₂₀ the temperature coefficient at 20 °C (1/°C) and T the temperature of the conductor (°C). For copper α = 0.00393: the resistance rises 0.393% per degree. That is why voltage drop tables use the resistivity at the maximum temperature of the insulation:
| Temperature | Copper (Ω·mm²/m) | Aluminum (Ω·mm²/m) | When it is used |
|---|---|---|---|
| 20 °C | 0.01724 (1/58) | 0.02826 (1/35.4) | Table value |
| 70 °C | 0.02063 (1/48.5) | 0.03396 (1/29.4) | PVC-insulated cable at full load |
| 90 °C | 0.02198 (1/45.5) | 0.03624 (1/27.6) | XLPE- or EPR-insulated cable at full load |
Worked example
A copper conductor 100 m long and 2.5 mm² at 20 °C:
At full load, with PVC insulation (70 °C):
Almost 20% more. In a single-phase line the current goes out and comes back, so the resistance of the circuit is that of 200 m: 1.65 Ω at 70 °C. With aluminum of the same cross-section at 20 °C it would be 1.1306 Ω per conductor.
Resistivity of materials
| Material | ρ at 20 °C (Ω·mm²/m) | α at 20 °C (1/°C) | Typical use |
|---|---|---|---|
| Silver | 0.0159 | 0.0038 | Contacts, brazing |
| Annealed copper (IEC 60028) | 0.017241 | 0.00393 | Cables and windings |
| Gold | 0.0244 | 0.0034 | Connector contacts |
| Cable aluminum (IEC 60889) | 0.028264 | 0.00403 | Overhead lines and distribution cables |
| Tungsten | 0.056 | 0.0045 | Lamp filaments |
| Zinc | 0.059 | 0.0037 | Galvanizing |
| Nickel | 0.0699 | 0.006 | Batteries, plating |
| Brass | 0.07 (from 0.06 to 0.09) | 0.0015 | Terminals and lugs |
| Iron | 0.0971 | 0.005 | Cores, structures |
| Platinum | 0.106 | 0.00392 | Temperature sensors (Pt100) |
| Tin | 0.109 | 0.0045 | Solder, tinned copper |
| Carbon steel | 0.143 | 0.003 | Ground rods, armor, ground wire |
| Lead | 0.22 | 0.0039 | Lead-acid batteries |
| Manganin | 0.482 | 0.000002 | Shunts and standard resistors |
| Constantan | 0.49 | 0.000008 | Type T and J thermocouples, precision resistors |
| Stainless steel | 0.69 | 0.00094 | Load resistors, structures |
| Nichrome (80% Ni, 20% Cr) | 1.10 | 0.0004 | Heating elements |
Copper and aluminum: values from the conductor standards. The rest are typical values from physics tables and manufacturers: each alloy (steels, brasses) varies. If you have the figure for your material, choose “Other” and type it in.
Resistance and cross-section of cables
The resistance of 1 km of copper cable at 20 °C, calculated with the formula (the cable standard, UNE-EN 60228, gives somewhat higher maximum values for stranded conductors):
| Cross-section (mm²) | 1.5 | 2.5 | 4 | 6 | 10 | 16 | 25 | 35 | 50 |
|---|---|---|---|---|---|---|---|---|---|
| Copper (Ω/km) | 11.49 | 6.90 | 4.31 | 2.87 | 1.72 | 1.08 | 0.690 | 0.493 | 0.345 |
| Aluminum (Ω/km) | 18.84 | 11.31 | 7.07 | 4.71 | 2.83 | 1.77 | 1.13 | 0.808 | 0.565 |
Frequently asked questions
What is the resistivity of copper?
The annealed copper used in cables has 0.017241 Ω·mm²/m at 20 °C (IEC 60028), that is, 1/58: a 1 mm² wire 58 m long has 1 Ω. The aluminum used in cables, 0.028264 Ω·mm²/m (1/35.4).
How much does resistance rise with temperature?
In copper, 0.393% per degree. From 20 °C to 70 °C (the maximum temperature of a PVC-insulated cable) it rises almost 20%, and at 90 °C (XLPE cable), 27.5%.
What length do I enter for a single-phase line?
The calculator gives the resistance of one conductor. The current goes out on the phase and comes back on the neutral, so the resistance of the circuit is that of 2 · L. In a balanced three-phase line you calculate one conductor.
Is the formula valid at any temperature?
The linear correction ρ = ρ₂₀ · [1 + α · (T − 20)] is good between about −50 °C and 200 °C for most metals. Very far from 20 °C the resistivity is no longer linear and you have to use tables for the material.
Why is nichrome used in heating elements?
Because its resistivity is about 64 times that of copper (1.1 Ω·mm²/m), it withstands red heat without oxidizing and its resistance barely changes with temperature (α = 0.0004). Constantan and manganin change even less and are used in precision resistors and shunts.
Related calculators
- Ohm's law calculator: voltage, current, resistance and power
- Voltage drop calculator and wire size
- AWG to mm² converter: wire gauge, cross-section and diameter
- Pt100, Pt500 and Pt1000 calculator: resistance to temperature
- Series and parallel resistor calculator (and capacitors)
- Electrical power calculator: active, reactive and apparent power and power factor