Wire resistance calculator: resistivity, length and cross-section

Calculate the resistance of a wire or conductor from its material, length, cross-section and temperature. Also solves for the length or the wire size.

Fill in 2 of the 3 fields and the missing one is calculated. You can type in any of them.

Filled in when you choose the material. If you type another value, the material changes to “Other”.
How much the resistivity rises per degree (0.00393 = 0.393% per °C for copper).
1/°C
A PVC-insulated cable runs at 70 °C at most; an XLPE one, at 90 °C.
The length of a single conductor. For out and back (phase and neutral), twice as much.
Resistivity at that temperature—
Conductivity—
Conductivity relative to standard copper (IACS)—
Resistance per unit length—
Resistance at 20 °C—
Diameter of a solid conductor of that cross-section—

Use this calculator for reference only, as we cannot guarantee that the results are free of errors.

Disclaimer

https://dyaii.es/en/wire-resistance-calculator/

Advertisement

Every conductor has resistance: more the longer it is, less the thicker it is, and it depends on the material and the temperature. This calculator gives you the resistance of a cable or a wire made of copper, aluminum, nichrome or any other material, corrected to its operating temperature, and also the other way around: what length or what cross-section gives a certain resistance. It is the first step in calculating the voltage drop and the losses of a line.

How to use the calculator

  1. Choose the material: its resistivity at 20 °C and its temperature coefficient are filled in. If it is not listed, choose “Other” and type the manufacturer's data.
  2. Enter the temperature of the conductor. At 20 °C the table resistivity is used as is; for a cable under load, use the operating temperature (70 °C with PVC, 90 °C with XLPE).
  3. Of length, cross-section and resistance, enter two: the third is calculated. Each one in the unit you want (m, km, ft; mm², cm², in²; mΩ, Ω…).
  4. In the drawing, the cable takes the color of the material, gets longer and thicker with the length and the cross-section, and the thermometer shows the temperature.

Wire resistance formula

R = ρ · L / S

Where R is the resistance (Ω), ρ the resistivity of the material (Ω·mm²/m), L the length (m) and S the cross-section (mm²). It is sometimes called Ohm's second law. In SI units the resistivity is in Ω·m and the cross-section in m² (1 Ω·mm²/m = 10⁻⁶ Ω·m). Solving for the others:

L = R · S / ρ · · · S = ρ · L / R

The reciprocal of resistivity is conductivity, σ = 1 / ρ, in S/m (or in m/(Ω·mm²), which is the same as MS/m). Copper has 58 MS/m.

Advertisement

Temperature correction

The resistivity of metals rises with temperature. Between about −50 °C and 200 °C it is corrected with a straight line:

ρ(T) = ρ₂₀ · [1 + α₂₀ · (T − 20)]

Where ρ₂₀ is the resistivity at 20 °C, α₂₀ the temperature coefficient at 20 °C (1/°C) and T the temperature of the conductor (°C). For copper α = 0.00393: the resistance rises 0.393% per degree. That is why voltage drop tables use the resistivity at the maximum temperature of the insulation:

TemperatureCopper (Ω·mm²/m)Aluminum (Ω·mm²/m)When it is used
20 °C0.01724 (1/58)0.02826 (1/35.4)Table value
70 °C0.02063 (1/48.5)0.03396 (1/29.4)PVC-insulated cable at full load
90 °C0.02198 (1/45.5)0.03624 (1/27.6)XLPE- or EPR-insulated cable at full load
The 70 °C and 90 °C values come from the formula above with the standard values at 20 °C. They are very close to the conductivities that the technical guide to Spain's low-voltage code (REBT) uses to calculate voltage drop (copper: 48 and 44 m/(Ω·mm²); aluminum: 30 and 28), which rounds them.

Worked example

A copper conductor 100 m long and 2.5 mm² at 20 °C:

R = 0.017241 · 100 / 2.5 = 0.6896 Ω

At full load, with PVC insulation (70 °C):

ρ(70) = 0.017241 · [1 + 0.00393 · (70 − 20)] = 0.020629 Ω·mm²/m
R = 0.020629 · 100 / 2.5 = 0.8252 Ω

Almost 20% more. In a single-phase line the current goes out and comes back, so the resistance of the circuit is that of 200 m: 1.65 Ω at 70 °C. With aluminum of the same cross-section at 20 °C it would be 1.1306 Ω per conductor.

Resistivity of materials

Materialρ at 20 °C (Ω·mm²/m)α at 20 °C (1/°C)Typical use
Silver0.01590.0038Contacts, brazing
Annealed copper (IEC 60028)0.0172410.00393Cables and windings
Gold0.02440.0034Connector contacts
Cable aluminum (IEC 60889)0.0282640.00403Overhead lines and distribution cables
Tungsten0.0560.0045Lamp filaments
Zinc0.0590.0037Galvanizing
Nickel0.06990.006Batteries, plating
Brass0.07 (from 0.06 to 0.09)0.0015Terminals and lugs
Iron0.09710.005Cores, structures
Platinum0.1060.00392Temperature sensors (Pt100)
Tin0.1090.0045Solder, tinned copper
Carbon steel0.1430.003Ground rods, armor, ground wire
Lead0.220.0039Lead-acid batteries
Manganin0.4820.000002Shunts and standard resistors
Constantan0.490.000008Type T and J thermocouples, precision resistors
Stainless steel0.690.00094Load resistors, structures
Nichrome (80% Ni, 20% Cr)1.100.0004Heating elements

Copper and aluminum: values from the conductor standards. The rest are typical values from physics tables and manufacturers: each alloy (steels, brasses) varies. If you have the figure for your material, choose “Other” and type it in.

Resistance and cross-section of cables

The resistance of 1 km of copper cable at 20 °C, calculated with the formula (the cable standard, UNE-EN 60228, gives somewhat higher maximum values for stranded conductors):

Cross-section (mm²)1.52.5461016253550
Copper (Ω/km)11.496.904.312.871.721.080.6900.4930.345
Aluminum (Ω/km)18.8411.317.074.712.831.771.130.8080.565
Advertisement

Frequently asked questions

What is the resistivity of copper?

The annealed copper used in cables has 0.017241 Ω·mm²/m at 20 °C (IEC 60028), that is, 1/58: a 1 mm² wire 58 m long has 1 Ω. The aluminum used in cables, 0.028264 Ω·mm²/m (1/35.4).

How much does resistance rise with temperature?

In copper, 0.393% per degree. From 20 °C to 70 °C (the maximum temperature of a PVC-insulated cable) it rises almost 20%, and at 90 °C (XLPE cable), 27.5%.

What length do I enter for a single-phase line?

The calculator gives the resistance of one conductor. The current goes out on the phase and comes back on the neutral, so the resistance of the circuit is that of 2 · L. In a balanced three-phase line you calculate one conductor.

Is the formula valid at any temperature?

The linear correction ρ = ρ₂₀ · [1 + α · (T − 20)] is good between about −50 °C and 200 °C for most metals. Very far from 20 °C the resistivity is no longer linear and you have to use tables for the material.

Why is nichrome used in heating elements?

Because its resistivity is about 64 times that of copper (1.1 Ω·mm²/m), it withstands red heat without oxidizing and its resistance barely changes with temperature (α = 0.0004). Constantan and manganin change even less and are used in precision resistors and shunts.